The 195N1047 low-voltage AC drive is manufactured by Danfoss within the VLT 2800 Low Voltage Drives series. Designed for process-oriented automation cells, it converts fixed mains power to a variable-frequency output that lets induction motors operate at commanded speed and torque. The drive supports cabinet or wall mounting and occupies minimal panel width, making it practical when multiple axes must share limited enclosure space.

The unit accepts a nominal input of 380-480 V ±10% at 50 or 60 Hz on a three-phase supply. Internally, the power section is rated for 1.5 kW, which corresponds to a mechanical shaft capacity of 2.0 HP when matched to a standard four-pole motor. This power range suits small pumps and agitators common in continuous-process industries. Thermal and electrical protection are coordinated with the enclosure's IP20 rating, so line-side guarding is still required while finger-safe operation is maintained inside a closed panel. The drive is delivered with standard hardware and no application option board, and it has no conformal coating for general-purpose process duties where ambient moisture or corrosive gases are not expected.

For operator interaction, a built-in display (SLCP) presents speed, alarms, and parameter values without needing an external keypad. Networked control is possible through the optional DeviceNet fieldbus card, allowing remote start, stop, and setpoint exchange with PLCs that manage plant-wide data layers. The slim book-style housing aligns power terminals at the bottom edge to streamline daisy-chain wiring. Radio-frequency emissions are limited by the integrated RFI filter that meets EN 55011 Class A1 limits, so additional line chokes are rarely required in industrial zones. The drive is configured for process applications, and dedicated option modules can be added later if extra functions are required.

Technical Specifications

Ambient Temperature Max
40°C
Application Option
No application option
Coating
Without coating
Communication Options
Profibus, DeviceNet, Modbus, Metasys N2
Dedicated Application
Process
Design
Metal Housing
Dimensions H X W X D
200 x 90 x 152 mm
Display
Built In Display (SLCP)
Enclosure Class
IP20
Enclosure Type
Bookstyle
Fieldbus Option
DeviceNet
Hardware Configuration
Standard
Horse Power
2.0 HP
Mains Voltage U(in)
380-480V +/- 10% 50/60Hz
Max Input Current
4.0 A
Max Output Frequency
120 Hz
Mounting
Vertical or Side-by-Side Mounting
Output Current (rated)
4.1 A
Phase
3 phase
Power Rating
1.5kW
Product Group
VLT
Protection Rating
IP20
RFI Filter
EN 55011 Class A1
Supply Frequency
50/60 Hz
Supply Voltage
3 x 380-480 V AC
Switching Frequency
4500 Hz
VLT Series
2800
Weight
3.8 kg

Click here for product datasheet

Contact Us

1620 Old Apex Road, Cary, NC 27513, USA

Toll Free: 1-888-551-3082

International: 1-919-443-0207

Fax: 1-919-867-6204

Email: sales@wakeindustrial.com

Shipping Options

DHL FedEx UPS Freight

Payment Methods

American Express MasterCard Visa Wire Transfer

Need Assistance?

Our team is here to help you find the right part for your needs.

Shipping logo

Worldwide Shipping with FedEx and UPS.

Payment logo

We accept all major credit cards

Warranty logo

1 year Automation Factory warranty on ALL products