Technical Specifications
Air Flow Rate (active)
9000m³/h (N+1 fan redundancy) 10800m³/h (no redundancy)
Altitude Above Sea Level
Max 2,000 m
Chilled Water Inlet Temperature
12 °C – 18 °C (53.6 °F – 64.4 °F)
Chilled Water Outlet Temperature
18 °C – 24 °C (64.4 °F – 75.2 °F)
Cooling Type
Passive and Active Rear Door
Dimensions (active)
77 in (1954mm) H x 23 in (420mm) W x 9 3/8 in (238mm) D
Max Power Consumption (active)
1185W
Maximum Operating Pressure
10 bar (145 psi)
Nominal Cooling Capacity
Up to 50 kW
Operating Temperature
+10…+40 °C
Power Consumption (active)
130W at 25kW power dissipation
Storage Temperature
-25…+80 °C
Weight (empty)
230 lbs (104.3 kg)