Technical Specifications
Certifications & Standards
CE, UL, cUL, CSA; EN61326-1 EMI; panel seal IP66/NEMA 4X
DC current output ranges
0-20 mA, 4-20 mA
DC voltage output ranges
0-5 V, 0-10 V, 2-10 V
Depth behind panel
100-110 mm
Low-voltage supply
20-48 VAC, 7.5 VA; 22-65 VDC, 5 W
Mains supply
100-240 VAC ±10%, 7.5 VA
Operating ambient temperature
0°C to 55°C
Panel cutout sizes
48×48, 96×48, 96×96 mm (1/16, 1/8, 1/4 DIN)
Pt100 input accuracy
±0.1% FSR, ±1 LSD (BS1904/DIN43760)
Relay output
SPDT, 2 A @120/240VAC, >500,000 ops
Remote setpoint accuracy
±0.25% of range, ±1 LSD
Serial communications
RS485, 1.2-19.2 kbps; Modbus or West ASCII
SSR driver output
>10 V into ≥500 Ω (≈20 mA)
Storage ambient temperature
-20°C to 80°C
Thermocouple input accuracy
±0.1% FSR, ±1 LSD (CJC error ~1°C)
Triac output
20-280 Vrms (47-63 Hz), 0.01-1 A (derate >40°C)
Universal input impedance
>10 MΩ; 5 Ω for mA; 47 kΩ for V
Universal input sampling rate
4 samples/s
Weight
0.21 kg