Technical Specifications
AC Supply Frequency
48–62 Hz
AC Supply Voltage
90–250 VAC
Cold Junction Comp. Error
±0.5 K
Control Modes
PID, 3-point stepping, 2-point on/off
Current Input Resistance
15 Ω
Display
PV LED 10.5 mm; lower LED 7.8 mm
Ingress Protection
Front IP65; Housing IP20; Terminals IP00
Mounting Method
Panel mount with two clamps; close mounting possible
Optional Supply Voltage
24 V AC/DC, output 22 mA/~18 V
Power Consumption
approx. 7 VA
Relay Output Rating
500 VA, 250 VAC, 2 A, 48–62 Hz, resistive
Resolution
>14 bit
Scanning Cycle
100 ms
Sensor Input Types
Thermocouples, Pt100/Pt1000, potentiometers
Temperature Ranges
Accuracy 0–60°C; Operating -20–65°C; Storage -40–70°C
Thermocouple Input Impedance
1 MΩ
Weight
0.27 kg