Technical Specifications
Cold Junction Compensation
Full module temperature range
Common-Mode Rejection
150 dB @ 60 Hz
Differential-Mode Rejection
7 dB @ 60 Hz
Input Channels
8 channels
Input Voltage Sensitivity
±100 mV max
J Type Thermocouple Ranges
-150°C to 1200°C; -35°C to 620°C; -10°C to 280°C
K Type Thermocouple Ranges
-200°C to 300°C; -80°C to 20°C; -35°C to 415°C
Manufacturer
Danaher
Measurement Accuracy
±100 mV or ±0.1% FS
Module Function
Measures J/K thermocouples or ±100 mV analog
Module Type
8-channel J-K thermocouple input block
Open Thermocouple Detection
Software indicated
Power Requirements
60 mA from 20–30 VDC (nominal 24 VDC)
Resolution
14-bit (13 bits + sign bit)
Sample Interval
47 ms
Thermocouple Accuracy
J: ±0.26% of 1350°C span; K: ±0.23% of 1500°C span