Technical Specifications
Status Indicators
Data transfer, M-Bus supply, operating status, module status
Module Run/error
Yes, using status LED and software
Data Transfer
Yes, using status LED
M-bus Power Supply
Yes, using status LED and software
Bus Power Consumption
0.2 W
Internal I/o Power Consumption
0.35 W + (number of slaves * 0.08 W)
Module Power Dissipation
0.55 W + (number of slaves * 0.006 W)
Isolation Voltage
500 VDC, 1 min between M-Bus and X2X Link
Interface Type
M-Bus master
Connection Variant
12-pin X20TB12 terminal block
Transfer Rate
300, 2400 or 9600 bit/s
Number Of Slaves
Max. 64
Internal Resistance Of Master
Max. 6 ?
Bus Voltage Mark
I/O supply voltage (+11.5 to 13.5 V)
Overload Shutdown
250 mA ~10%