Integrated X2x Link
Yes
Integrated Braking Chopper
Yes
Power Supply
Single phase 200 -15% to 240 +10% VAC, 50 to 60 Hz ~5%; Three phase 200 -15% to 240 +10% VAC, 50 to 60 Hz ~5%; Three phase 380 -15% to 500 +10% VAC, 50 to 60 Hz ~5%
Integrated Emc Filter Iec/en61800-3 Category C2
Yes
Integrated Emc Filter Iec/en61800-3 Category C3
Yes
Power Rating [kw]
0.18, 0.37, 0.55, 0.75, 1.1, 1.5, 2.2, 3, 4, 5.5, 7.5, 11, 15
Power Rating [hp]
0.25, 0.5, 0.75, 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20
Nominal Current [a] At Nominal Switching Frequency
1.5, 3.3, 3.7, 4.8, 6.9, 8, 11, 13.7, 17.5, 27.5, 33, 54, 66
Maximum Transient Current [a]
150% of nominal drive current for 60 s
Output Frequency
0.5 to 500 Hz
Switching Frequency
2 to 16 kHz, 4 kHz nominal
Transient Overtorque
170 to 200% of nominal motor torque (typical value)
Braking Torque - Without Braking Resistor
% of nominal motor torque (typical value): 150%, 100%, 50%, 30%
Braking Torque - With Braking Resistor
100% of nominal motor torque continuously and up to 150% for 60 s
Motor Control
Sensorless flux vector control, specific ratio for pumps and fans, energy saving, constant torque voltage/frequency ratio