The IE1011-0000 extension box is produced by Beckhoff as part of the IE Extension Box Units series. Serving as a digital input block for industrial automation systems, it routes discrete sensor signals directly into decentralized control networks. The module functions as a digital input device, allowing a controller to monitor on-machine limit switches, optical sensors, or push buttons while keeping the wiring localized at the equipment. Its sealed construction and IP-rated metal housing permit installation in any orientation, so it can be fastened to a frame, placed inside a drag chain, or mounted beside actuators without an additional enclosure.
Each channel operates at a nominal logic level of 24 VDC and draws only 6 mA, minimizing the load on proximity switches. A hardware debounce stage with a 0.2 ms filter suppresses mechanical contact chatter before the signal reaches the process image. Compliance with EN 61131-2 Type 2 allows the inputs to accept sourcing or sinking field devices within the specified current window. Internal control and fieldbus isolation separates the 24-volt sensor domain from the bus transceiver, protecting the upstream controller from electrical noise or wiring faults. Sensor power is derived from the US control-voltage rail. Channel states are transmitted to the controller for use in machine sequences, status monitoring, and fault detection.
Signal wiring is handled through 8 inputs connected to M8 screw-in sockets. A dedicated downstream M8 socket carries the field I/O extension to the next device, while a second four-pin M8 connector delivers the power feed and supports daisy-chaining along the machine. The module provides a sensor supply of 0.5 A per channel, so most inductive or capacitive sensors can be powered directly from the box. Data is presented to the controller as an 8-bit input image, keeping software addressing simple. Flexible positioning allows cable strain relief and connector accessibility to be arranged for the available machine space.
Technical Specifications
Control/fieldbus Isolation
Yes
Current consumption (without sensor current)
25 mA
Downstream Connector
1 x M8 Socket, 4-Pin
Input connections
M8, screw type
Input Count
8
Input Current
6 mA
Input current (typ.)
6 mA (EN 61131-2, type 2)
Input filter
0.2 ms
Input Standard
EN 61131-2 Type 2
Installation Position
Variable
Module Function
Digital Input
Nominal input voltage
24 VDC
Number of inputs
8
Operating temperature
0...55°C
Power Feed Connector
1 x M8 Connector, 4-Pin
Power supply connection (downstream)
1 x M8 female socket, 4-pin, a-coded
Power supply connection (feed)
1 x M8 male socket, 4-pin, a-coded
Process Image Width
8 Bits Input
Protection rating
IP65/66/67 (EN 60529)
Sensor supply
0.5 A Per Channel
Sensor Supply Source
Control Voltage US
Signal Connection
M8 Screw-In
Signal voltage '0' level
-3...+5 V (EN 61131-2, type 2)
Signal voltage '1' level
11...30 V (EN 61131-2, type 2)
Storage temperature
-25...+85°C