The ELX3202 is a twin-channel resistance temperature detector input terminal produced by Beckhoff within the EL EtherCAT Terminals series. It connects directly to the EtherCAT I/O system to deliver temperature data to a controller without intermediary signal conditioning. Designed for use with Pt100, Pt1000, and KTY sensors, it converts sensor resistance into a digital value that can be processed in automation routines. By occupying only one terminal slice, the unit allows compact, distributed temperature acquisition on production machines and process skids.
Each channel accepts two-, three-, or four-wire sensing loops; this flexible wiring is indicated by the 2-/3-/4-wire connection method and permits precise compensation of lead resistance. Internal electronics draw their logic power from the E-bus at 5 VDC, while the galvanically isolated field circuit is limited to 12 mA of short-circuit current and 15 mW of maximum power. These parameters meet intrinsic safety requirements when the 24 V Ex supply is used. The open-circuit voltage at the sensor never exceeds 4.94 V, helping prevent excess energy from entering hazardous areas. A linear characteristic curve simplifies scaling because the raw resistance is converted directly into a proportional temperature word.
The terminal samples both differential inputs with a resolution of 0.1 °C/digit, and the measuring current remains below 1 mA, preventing self-heating of delicate probes. Absolute accuracy remains within ±0.3% of full scale across the stated temperature span, including converter linearity and reference drift. Converted values are delivered to the controller as a 2 × 32-bit RTD process image, so no additional data packing is needed. The housing has an IP20 protection rating for installation in control cabinets, and status LEDs report channel conditions and sensor faults.
Technical Specifications
Bus Power Supply
via E-bus
Characteristic Curve
Linear
Configurable Connection Method
yes
Connection Method
2-/3-/4-wire
Conversion Time
10-3300 ms adjustable (default: 170 ms)
Current Consumption (E-bus)
typ. 70 mA
Current Consumption (power contacts)
typ. 10 mA
Digital Filter & Curve Linearization
integrated
E-bus Supply
5 VDC
Field Interface Io
12 mA
Field Interface Po
15 mW
Field Interface Uo
4.94 V
Input Filter Limit Frequency
typ. 1 kHz
Internal Resistance (differential)
>= 10 k?
Kty Support
KT(Y) sensors
Limit Monitoring
integrated
Measurement Uncertainty
±0.3% of full scale
Measuring Current
< 1 mA
Measuring Error
< ±0.3 % Full Scale
Number of Inputs
2 (differential)
Power Contact Supply
24 VDC Ex
Process Image
2 x 32 bit RTD input
Protection Class
IP20
Resistance Measurement Range
10 to 4000 ?
Resolution
0.1 °C/digit
Supply Voltage (electronics)
24 V DC via power contacts
Supported RTD Sensors
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, KT(Y)
Temperature Range
-200 to +850 °C (Pt); -60 to +250 °C (Ni)