The ELX1052 digital input module is built by Beckhoff as part of the EL EtherCAT Terminals series. It accepts intrinsically safe field signals and transmits them over the EtherCAT bus, enabling compact, panel-mounted I/O expansion in automated plants. By embedding explosion-zone sensor wiring into the standard DIN-rail terminal row, the module reduces remote junction boxes and speeds up commissioning in distributed control systems.
The terminal electronics draw power from the EtherCAT backplane at 24 V DC, so no auxiliary supply lines are required. It offers 2 intrinsically safe inputs that follow the 2-Wire NAMUR principle; each channel can therefore detect both current flow and lead integrity through the same conductors. A low-level current of <= 1.2 mA is interpreted as logic "0," while a drive of >= 2.1 mA registers as logic "1." These fixed thresholds let the PLC discriminate clear off and on states even when long sensor cables are used. Two blade/spring power contacts relay the supply across neighboring terminals, and wiring is performed by spring actuation with a screwdriver to shorten installation time and eliminate twisting of stranded cores.
In normal operation the terminal occupies only 12 x 100 x 68 mm, so several units can be arranged side by side on a 35 mm DIN rail (EN 60715) using the double slot and key profile without widening the control cabinet. The polycarbonate housing is rated IP20, providing finger protection in enclosed panels. Diagnostic functions compare the sensor loop against a cable-break limit of <= 200 µA and a short-circuit threshold of >= 6.3 mA, allowing the controller to flag wiring faults immediately. Continuous power bridging is maintained by the integrated blade contacts even when terminals are exchanged hot-plug.
Technical Specifications
"0" Signal Current
<= 1.2 mA
"1" Signal Current
>= 2.1 mA
"0" Signal Current
<= 1.2 mA
"1" Signal Current
>= 2.1 mA
Cable Break Threshold
<= 200 µA
Connection Method
2-Wire
Current Consumption E-bus
Typical 50 mA
Current Consumption Power Contacts
Typical 10 mA + load
Dimensions (w X H X D)
12 x 100 x 68 mm
Fault Detection
I <= 200 µA (cable break), I >= 6.3 mA (short circuit)
Housing Material
Polycarbonate
Installation
35 mm DIN Rail (EN 60715)
Max. Switching Frequency
Typical 50 Hz (duty factor 50%)
Number Of Inputs
2
Open Circuit Voltage
Typical 8.2 V DC
Power Contacts
2 Blade/Spring Contacts
Protection Rating
IP20
Short-circuit Current
Typical 8.2 mA
Short-circuit Threshold
>= 6.3 mA
Side-by-side Mounting
Double Slot & Key
Specification
NAMUR (IEC 60947-5-6)
Supply Voltage (electronics)
24 V DC
Supply Voltage Electronics
24 V DC (via power contacts), ELX9560 power supply
Switching Hysteresis
Typical 200 µA
Warranty
One-year
Weight
Approx. 55 g
Wiring
Spring Actuation By Screwdriver