EK1122 by Beckhoff

Rated 4.9 stars (16 reviews)

Get a Quote for EK1122

Request a quote or call us now at 1-888-551-3082!

In-Stock, Ships Today

We respect your privacy. Your information is safe and will never be shared.

Secure Online
Checkout

Free Ground
Shipping

One Year
Warranty

The EK1122 is a dual-junction EtherCAT coupler produced by Beckhoff and supplied under the EK EtherCAT Couplers series. In an automation cell, the unit serves as a network branch point, allowing two subordinate lines to attach to the primary EtherCAT trunk while continuing the internal E-bus to downstream I/O terminals. By performing this distribution within the DIN-rail footprint, it removes the need for external switches and simplifies cabinet wiring.

Each junction uses the branch sequence 1->2->E-bus, so incoming frames are forwarded first to junction 1, then to junction 2, and finally to the backplane bus that links additional terminals. The device provides two independent branches, enabling point-to-point connections or localized subnets inside the machine. Its enclosure carries the IP20 protection class, indicating finger-safe terminals and suitability for installation inside a control cabinet. The network uses a star topology, meaning both outgoing ports behave as individual node roots rather than as a line extension. When neither branch is cabled, the internal logic keeps communication active by maintaining a bridge between junctions 1 and 2, preventing an inadvertent link break.

Compatibility with networks using distributed clock synchronization begins at revision -0017 with FW 01. Earlier hardware revisions cannot generate DC reference signals, but they still pass EtherCAT traffic transparently through the connected branches. Because EtherCAT timing can be handled by upstream devices on the primary trunk, the coupler operates with no distributed clocks of its own and does not introduce additional jitter. The module is non-hot-swappable, so power must be removed before insertion or removal to avoid interrupting the EtherCAT ring. The housing follows the mounting dimensions used by other EK modules, allowing aligned installation on the same DIN rail.

Technical Specifications

Branch Order
1->2->E-bus

Dc Support Start
Rev -0017 / FW 01

Distributed Clocks Required
No

Hot Swap
No

Junction Count
2

Protection Class
IP20

Topology Use
Star

Unused Ports State
Junctions 1 And 2 Bridged

Click here for product datasheet

Contact Us

1620 Old Apex Road, Cary, NC 27513, USA

Toll Free: 1-888-551-3082

International: 1-919-443-0207

Fax: 1-919-867-6204

Email: sales@wakeindustrial.com

Shipping Options

DHLFedExUPSFreight

Payment Methods

American ExpressMasterCardVisaWire Transfer

Need Assistance?

Our team is here to help you find the right part for your needs.

Worldwide Shipping with FedEx and UPS.

We accept all major credit cards

1 year Automation Factory warranty on ALL products